    Fire Alarm Testing Requirements

    For non-domestic systems, the Fire Safety Order requires suitable maintenance but does not set one interval for every building. The Fire Industry Association says BS 5839-1 recommends risk-based inspection and servicing visits no more than six months apart, alongside routine user testing.

    Why Testing Matters

    A fire alarm that has never been tested may not work when a real fire occurs. Detectors accumulate contamination, batteries discharge and connections can deteriorate. The responsible person should arrange routine checks and servicing suited to the system, building and risk.

    The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person to maintain fire alarm equipment in an efficient state and working order. It does not itself prescribe a universal numerical service interval. See our plain-English maintenance guide for the current standard and source links.

    7

    Weekly

    Nominated member of staff (trained)

    Operate one manual call point using a test key or appropriate test instrument. Rotate through different call points each week so all points are tested over time.
    Verify that all sounders (and visual alarms where fitted) operate correctly when the call point is activated.
    Check the control panel display for any fault indicators. If faults are present, investigate and rectify or notify the service company.
    Reset the panel after the test.
    Record the date, time, call point tested and result in the fire alarm log book.
    6M

    Periodic service — no more than six months apart

    Competent fire alarm engineer (SSAIB or equivalent accredited company)

    Inspect and test a representative sample of automatic detectors — smoke, heat and multi-sensor. Where practical, all detectors should be tested across the two six-monthly visits.
    Test all manual call points in rotation.
    Test all sounders and alarm devices, including visual alarm devices.
    Test the control and indicating equipment — all functions including alarm, fault, isolate and reset.
    Check all standby batteries — voltage, current and condition.
    Test the mains power supply.
    Inspect all cables, connections and cable fixings for visible damage or deterioration.
    Test any remote transmission equipment (monitoring link).
    Review and update the log book. Issue a service record to the responsible person.
    +

    Additional visits when the risk or condition requires

    Competent fire alarm engineer

    Arrange an earlier visit if faults, repeated false alarms, damage or environmental changes affect system reliability.
    Review the system after changes to the building, occupancy, layout or use.
    Follow any shorter interval required by the risk assessment, insurer or manufacturer.
    Keep the findings and any remedial actions in the system records.

    The Log Book

    Every test must be recorded. The log book is the primary evidence that the responsible person has met their maintenance duty. It must capture:

    • Date and time of each test
    • Which call point or detector was tested
    • The result (pass or fail)
    • Any faults found and the corrective action taken
    • Any false alarms — time, zone, cause, action
    • Engineer visits — name, company, work carried out

    The log book must be kept on the premises and available for inspection. It may be paper-based or electronic. Gaps in the log book are treated as evidence of non-compliance during fire authority inspections.

    When to Notify the Monitoring Centre

    If the system is connected to a remote monitoring centre (an alarm receiving centre), the monitoring centre must be informed before any test is carried out that will generate an alarm signal. Failure to do so may result in an unnecessary emergency call. After the test, the monitoring centre should be notified that the test is complete and the system is back in normal operation.

    Testing During Occupied Hours

    Weekly tests should be carried out at a time when the building is normally occupied so that the test simulates a real alarm condition. Staff should be aware that a test is taking place. The same call point should not be used for every weekly test — rotate around all call points over time.

    Planned Preventive Maintenance Contracts