Fire Alarm Testing Requirements
For non-domestic systems, the Fire Safety Order requires suitable maintenance but does not set one interval for every building. The Fire Industry Association says BS 5839-1 recommends risk-based inspection and servicing visits no more than six months apart, alongside routine user testing.
Why Testing Matters
A fire alarm that has never been tested may not work when a real fire occurs. Detectors accumulate contamination, batteries discharge and connections can deteriorate. The responsible person should arrange routine checks and servicing suited to the system, building and risk.
The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person to maintain fire alarm equipment in an efficient state and working order. It does not itself prescribe a universal numerical service interval. See our plain-English maintenance guide for the current standard and source links.
Weekly
Nominated member of staff (trained)
Periodic service — no more than six months apart
Competent fire alarm engineer (SSAIB or equivalent accredited company)
Additional visits when the risk or condition requires
Competent fire alarm engineer
The Log Book
Every test must be recorded. The log book is the primary evidence that the responsible person has met their maintenance duty. It must capture:
- Date and time of each test
- Which call point or detector was tested
- The result (pass or fail)
- Any faults found and the corrective action taken
- Any false alarms — time, zone, cause, action
- Engineer visits — name, company, work carried out
The log book must be kept on the premises and available for inspection. It may be paper-based or electronic. Gaps in the log book are treated as evidence of non-compliance during fire authority inspections.
When to Notify the Monitoring Centre
If the system is connected to a remote monitoring centre (an alarm receiving centre), the monitoring centre must be informed before any test is carried out that will generate an alarm signal. Failure to do so may result in an unnecessary emergency call. After the test, the monitoring centre should be notified that the test is complete and the system is back in normal operation.
Testing During Occupied Hours
Weekly tests should be carried out at a time when the building is normally occupied so that the test simulates a real alarm condition. Staff should be aware that a test is taking place. The same call point should not be used for every weekly test — rotate around all call points over time.