    Fire Alarm Maintenance: What Does the Law Require?

    The legal obligations for fire alarm maintenance — the Regulatory Reform (Fire Safety) Order 2005, BS 5839-1 service intervals, what the responsible person must do, and what records must be kept.

    The Legal Duty: The Regulatory Reform (Fire Safety) Order 2005

    The Regulatory Reform (Fire Safety) Order 2005 (RRO) is the primary fire safety legislation for non-domestic premises in England and Wales. Under Article 17 of the RRO, the responsible person must ensure that:

    • Any facilities, equipment and devices provided for fire detection and alarm are subject to a suitable system of maintenance
    • They are maintained in an efficient state, efficient working order and good repair

    The Fire Safety Order does not set one service interval for every building. It requires a suitable maintenance system. BS 5839-1:2025 is the current code of practice for non-domestic systems; the Fire Industry Association says inspection and servicing intervals should be risk-based and should not exceed six months. A higher-risk environment or insurer requirement may call for more frequent attention.

    What BS 5839-1:2025 Requires

    In plain English: the responsible person should arrange routine user checks and keep a competent engineer's inspection and servicing visits no more than six months apart, unless the risk assessment, system or insurer calls for a shorter interval. Check the current standard and system-specific instructions when setting the schedule.

    Weekly

    Responsible person / nominated staff

    • Test one manual call point by rotating test key or using a magnet (for addressable systems)
    • Confirm sounders operate correctly
    • Check the control panel for faults and clear any fault conditions
    • Record the test in the fire alarm log book

    Periodic engineer visit — no more than six months apart

    Competent fire alarm engineer

    • Inspect and service the system in line with its design, current standard and manufacturer's instructions
    • Test detectors, call points, alarm devices, control equipment, power supplies and monitoring as appropriate
    • Review reported faults, false alarms, changes to the building and any outstanding remedial work
    • Record the work and findings in the log book and provide a service record

    The Fire Alarm Log Book

    BS 5839-1 requires that a log book is maintained for every fire alarm system. The log book must record:

    • All tests carried out — date, time, the call point or detector tested and the result
    • All false alarms — date, time, zone, cause (if identified) and action taken
    • All faults — date detected, nature of fault, and date and nature of the repair
    • All visits by the service company — date, work carried out and name of the engineer
    • Any alterations or extensions to the system

    The log book may be paper or electronic. It must be available for inspection by the fire authority, building control or insurance surveyor on request. A missing or incomplete log book is often the first issue identified during a fire authority audit.

    Who Can Carry Out Maintenance?

    The routine user test can be carried out by a nominated, trained member of staff. Periodic inspection and servicing should be carried out by a competent fire alarm engineer — someone with the knowledge, skills and experience to work on the system and follow the current standard and manufacturer's instructions.

    SSAIB-accredited companies like MA Fire and Security Systems provide engineers who are assessed against third-party certification standards. Using an accredited company provides the responsible person with evidence that the maintenance duty is being met by a verified competent organisation.

    What Happens if Maintenance Is Not Carried Out?

    Failure to maintain a fire alarm system to the required standard can result in:

    • Enforcement notices from the local fire authority
    • Prosecution of the responsible person under the RRO (unlimited fine; up to two years imprisonment for serious failures)
    • Invalidation of buildings insurance
    • Invalidated fire certificate (for premises that hold one)
    • Personal liability if a fire occurs and the system fails

    Sources and further reading

    This guide is a practical summary, not a substitute for the full standard, a fire risk assessment or competent advice for a particular premises.

    Landlords and HMO Proprietors

    Domestic fire alarm systems in rented properties are covered by BS 5839-6 and specific housing legislation. See our Landlord Compliance guide for specific requirements.

    Fire Alarm Servicing Across Essex & London

    Risk-based inspections at intervals no longer than six months, with service records and log-book support.